Dry Type Transformers

Dry Type Cast Resin Transformers Upto 10 MVA, 36 KV Class

TMC India manufactures VPI & cast resin transformers designed to meet customer specifications and various national and international standards. The range includes distribution & medium power transformers up to 10 MVA, 36 kV class with class F (or) Class H temperature class of insulation. The design and process followed in TMC ensures very low level of partial discharges.

TMC India is the only manufacturer in India to conduct E2-C2-F1 test on transformer as per IEC 60076-11 issued in 2018.

Special Features:
  • E2 C2 F1 certification
  • Foil winding in Low voltage and High voltage windings
  • Copper / Aluminum windings as specified
  • High permeability core laminations with step-lap construction
  • Losses as per latest issue of ECBC 2017
  • Enclosure protection class upto IP44
  • Transformers with OLTC upto 36 KV class

Advantages Of Cast Resin Transformers:

  • Highly resistant to fire and self-extinguishable
  • Non-toxicity of combustion gases in case of fire
  • can be used in highly humid and polluted environments
  • Non hygroscopic insulation provide longer life expectancy
  • Not required to wait long periods to load transformer
  • Not required to provide special arrangement for fire barriers & oil catchment etc.
  • Low installation costs
  • No maintenance required compared to oil filled transformers
  • Low losses of the operation , thanks to the possibility of installing transformers in proximity of the load
  • High resistance to short circuit stress
  • High resistance to over voltage
  • High insulation degree and no partial discharges

Application Areas:

  • Power Distribution
  • Converter/Inverter applications
  • Renewable energy (Wind & Solar)
  • Traction applications
  • Oil & Gas Offshore platform
  • Industrial cranes
  • Seismic Conditions

DRY TYPE TRANSFORMERS – LOSSES AS PER ECBC GUIDE 2017


RATING
KVA
MAX. LOSSES AT 50 % LOADING WATTS MAX. LOSSES AT 100 % LOADING WATTS MAX. LOSSES AT 50 % LOADING WATTS MAX. LOSSES AT 100 % LOADING WATTS
UPTO 22 KV CLASS 33 KV CLASS
100 940 2400 1120 2400
160 1290 3300 1420 3300
200 1500 3800 1750 4000
250 1700 4320 1970 4600
315 2000 5040 2400 5400
400 2380 6040 2900 6800
500 2800 7250 3300 7800
630 3340 8820 3950 9200
800 3880 10240 4650 11400
1000 4500 12000 5300 12800
1250 5190 13870 6250 14500
1600 6320 16800 7500 18000
2000 7500 20000 8880 21400
2500 9250 24750 10750 26500

# Reference temperature for Load Losses 120°C
# lndicative data. We reserve the right to modify the data without prior information.