Oil Type Transformers

Oil Filled Transformers Upto 50 MVA, 132 KV Class

TMC India manufactures wide range of oil filled transformers designed to meet the specification and various national and international standards. The range includes distribution & medium power transformers up to 50 MVA, 132 kV class.

Special Features:
  • Designs to meet various national and international standards
  • Mineral Oil, Silicon Oil, Ester Oil as per customer requirement
  • Copper / Aluminum windings as specified
  • High permeability core laminations with step-lap construction
  • Losses as per IS 1180 upto 2500 KVA
  • Conventional type and hermitically sealed tank construction

Special application transformers

  • Converter/inverter duty
  • Furnace duty
  • Neutral grounding transformers
  • Auto transformers

OIL FILLED TRANSFORMERS – LOSSES AS PER IS:1180


KVA
% Z
11/0.433
LEVEL-1 
LEVEL-2
LEVEL-3
50 % LOAD
WATTS
100 % LOAD
WATTS
50 % LOAD
WATTS
100 % LOAD
WATTS
50 % LOAD
WATTS
100 % LOAD
WATTS
250
4.5
1050
3150
980
2930
920
2700
315
4.5
1100
3275
1025
3100
955
2750
400
4.5
1300
3875
1225
3450
1150
3330
500
4.5
1600
4750
1510
4300
1430
4100
630
4.5
2000
5855
1860
5300
1745
4850
800
5
2459
7300
2287
6402
2147
5837
1000
5
3000
9000
2790
7700
2620
7000
1250
5
3600
10750
3300
9200
3220
8400
1600
6.25
4500
13500
4200
11800
3970
11300
2000
6.25
5400
17000
5050
15000
4790
14100
2500
6.25
6500
20000
6150
18500
5900
17500

# For 22 KV Class : Total loss value shall not exceed by 5% of above mentioed values.